Legionella Risk Assessment Legal Requirements are the duties set by UK health and safety law to identify and evaluate the risk of exposure to legionella bacteria from work activities and water systems, and to determine the measures needed to prevent or control that risk. The core duties arise under the Control of Substances Hazardous to Health Regulations 2002 (COSHH) regulation 6, the Management of Health and Safety at Work Regulations 1999 (MHSWR) regulation 3, and sections 2, 3 and 4 of the Health and Safety at Work etc. Act 1974 (HSWA).

HSE’s ACOP L8 and HSG274 set the recognised approach for cooling towers, hot and cold water systems and other aerosol‑generating systems. Dutyholders must ensure assessments are suitable and sufficient, implemented through a written scheme, and kept under review.

Purpose & Scope Of The Regulation

Legionella Risk Assessment Legal Requirements ensure dutyholders identify whether there is a reasonably foreseeable risk of exposure to legionella from their undertaking and, where risk exists, prevent exposure or, if prevention is not reasonably practicable, adequately control it.

  • COSHH regulation 6 requires a suitable and sufficient assessment of the risks to health created by work liable to expose persons to a substance hazardous to health (including biological agents such as legionella) before that work is carried out. It also requires assessment of risks to non‑employees who may be affected and review when circumstances change.
  • MHSWR regulation 3 requires a suitable and sufficient assessment of risks to employees and others arising out of or in connection with the employer’s undertaking, recording significant findings where five or more employees are employed, and reviewing when no longer valid or after a significant change.
  • HSWA sections 2, 3 and 4 impose general duties to ensure, so far as is reasonably practicable, the health and safety of employees (section 2), the health and safety of non‑employees affected by the undertaking (section 3), and duties on those in control of premises towards non‑employees (section 4).
  • HSE’s Approved Code of Practice L8 and guidance HSG274 Parts 1–3 explain how to comply in practice, including risk assessment, competent assistance, schematics and asset registers, written schemes of control, monitoring, record‑keeping and review.

Scope: All relevant water systems and activities that can support legionella growth and generate aerosols, including cooling towers and evaporative condensers, domestic hot and cold water systems (tanks, calorifiers, distribution, outlets, showers, thermostatic mixing valves), and spa pools. The assessment must consider the whole installation, including parts temporarily out of use, dead legs and seldom‑used outlets, and evaluate normal and reasonably foreseeable abnormal conditions in line with Legionella Risk Assessment Legal Requirements.

Who Must Comply

Legionella Risk Assessment Legal Requirements apply to the dutyholder responsible for ensuring a suitable and sufficient assessment is undertaken and acted upon. Depending on the circumstances, this will be:

  • The employer, where risks from the undertaking may affect employees or others (HSWA sections 2–3; COSHH regulation 6; MHSWR regulation 3).
  • A self‑employed person, where the undertaking presents a risk to themselves or others (HSWA section 3; COSHH regulation 6).
  • The person in control of premises or systems in connection with work, where there is a risk from systems in the building; for example, a landlord who retains responsibility for maintaining the water system in a multi‑let building (HSWA section 4; HSE ACOP L8).

In practice, building owners and landlords with retained maintenance duties, managing agents and facilities managers, employers operating process water or cooling systems, and organisations responsible for healthcare, residential and nursing homes will need to comply with the Legionella Risk Assessment Legal Requirements. Employers must also consult employees or their representatives on arrangements for competent assistance and on identified risks and control measures. Source: HSE consultation guidance.

Key Compliance Requirements

Risk Assessment Competence And Governance

Dutyholders must ensure the legionella risk assessment is carried out by a competent person and overseen by a responsible person with sufficient authority and resources. This is central to the Legionella Risk Assessment Legal Requirements. Actions include:

  • Identify the legal dutyholder (employer, self‑employed, or person in control of premises/systems).
  • Appoint a competent person to conduct the assessment and advise on prevention and control (COSHH regulation 6; MHSWR regulation 7). Competence requires appropriate training, experience and knowledge of Legionella control and site‑specific systems. Competence may be internal or external (e.g. specialist consultant or water treatment provider). Make reasonable enquiries to verify competence and equipment suitability.
  • Nominate a responsible person to implement the written scheme and manage ongoing control, with deputies for continuity (HSE ACOP L8).

Scope Definition And Information Gathering

Define the scope so all systems and activities that could present a Legionella risk are included:

  • Cooling towers and evaporative condensers (HSG274 Part 1).
  • Domestic hot and cold water services, including cold water storage tanks, calorifiers, plate heat exchangers, distribution pipework, outlets/taps, showers and thermostatic mixing valves (TMVs) (HSG274 Part 2).
  • Spa pools and similar aerosol‑generating systems (HSG274 Part 3).
  • Other site‑specific water systems capable of generating aerosols.

Collect as‑installed details, O&M manuals, historical monitoring/sampling results, water source information, occupancy/use patterns and information on vulnerable user groups. This evidence base supports compliance with the Legionella Risk Assessment Legal Requirements.

Site Survey And Asset Register

Survey the site and consider each relevant system as a whole rather than isolated components. Compile a comprehensive asset register of storage vessels, heaters/calorifiers, heat exchangers, pumps, valves, strainers/filters, dosing and disinfection equipment, outlets and showers, TMVs, and pipework sections including dead legs and low‑use outlets. Include items temporarily isolated or out of use.

Schematic Diagrams

Produce clear, up‑to‑date schematics for each relevant system showing the layout, relative positions and connections of key components and flow paths, including parts temporarily out of use. Schematics are intended to be readable without specialist training and are essential to plan inspection, monitoring and control.

Hazard Identification And Exposure Evaluation

Evaluate factors that create a risk of legionellosis:

  • Conditions for growth: water temperatures typically between 20 °C and 45 °C; nutrient sources such as sludge, scale, rust, algae, organic matter and biofilms; stagnation; low or intermittent use; materials compatibility.
  • Aerosol generation and dispersion: cooling towers, evaporative condensers, showers, spa pools and spray taps, and potential for inhalation by occupants and workers.
  • Exposure and susceptibility: numbers of people who may be exposed, including higher‑risk groups in healthcare, residential and nursing homes.
  • Operational conditions: normal parameters and reasonably foreseeable deviations (e.g. breakdowns, extended low occupancy, and recommissioning after shutdown).

Dead legs and intermittently used sections require particular attention because microbial growth can go unnoticed and cause heavy contamination when brought back online.

Determining Reasonably Foreseeable Risk

Assess the likelihood and potential severity of harm and decide whether harm is reasonably foreseeable unless adequate precautions are taken (COSHH regulation 6; MHSWR regulation 3). Where no reasonably foreseeable risk exists, or risks are insignificant and unlikely to increase when properly managed, further measures may not be necessary beyond periodic review. Record the conclusion and supporting evidence. Review the assessment if circumstances change, in line with the Legionella Risk Assessment Legal Requirements.

Prevention First

Apply the hierarchy of control and prevent exposure where reasonably practicable by:

  • Eliminating redundant pipework and dead legs.
  • Designing out or decommissioning unnecessary aerosol‑generating features.
  • Minimising unnecessary storage and improving circulation to avoid stagnation.
  • Selecting materials compatible with the intended disinfection regime. Prevention measures should be built into new designs and refurbishments and, where practicable, retrofitted to existing systems.

Control Measures Where Prevention Is Not Practicable

Where exposure cannot be prevented, implement proportionate controls via a written scheme:

  • Temperature control: for domestic systems, HSG274 Part 2 describes typical control parameters (e.g. cold water below 20 °C at outlets; hot water stored at 60 °C and distributed so that outlets reach at least 50 °C within one minute, or 55 °C in healthcare premises).
  • Secondary disinfection for domestic systems where indicated (e.g. continuous dosing or periodic disinfection).
  • Cooling tower water treatment: robust biocide dosing (oxidising/non‑oxidising), bleed/blowdown control, corrosion/scale inhibition, with routine monitoring and microbiological testing (HSG274 Part 1).
  • Physical cleaning and descaling; inspection and maintenance of tanks, calorifiers and strainers to remove nutrients and biofilms.
  • Planned flushing of low‑use outlets; controlled isolation of unused outlets; documented recommissioning procedures.
  • Safe start‑up/shutdown arrangements and controls to minimise aerosol release and exposure.

These measures translate the Legionella Risk Assessment Legal Requirements into practical, auditable controls.

Roles, Responsibilities And Training

Document responsibilities for management oversight, monitoring and inspection, sampling, data review, corrective actions, documentation and contractor control. Provide information, instruction and training so staff can perform assigned tasks competently (e.g. flushing, temperature checks, sampling, cleaning). Ensure escalation procedures are clear when alert/action levels are exceeded. Consult employees or their representatives on identified risks, control measures and arrangements for competent help. Source: HSE consultation guidance.

Monitoring, Inspection And Testing

Define what will be monitored, how and how often, proportionate to risk and system complexity:

  • Domestic hot and cold water systems: temperature profiling; inspection of tanks and calorifiers; verification of flushing at low‑use outlets; visual checks for scale and biofilm; microbiological sampling where indicated by risk.
  • Cooling towers/evaporative condensers: water chemistry, biocide residuals, conductivity/bleed control, corrosion/scale indicators; visual inspection for fouling; routine microbiological testing to validate and verify control (HSG274 Part 1).

Set alert and action levels with predetermined corrective actions, responsibilities and timescales. Maintain and calibrate measurement and sampling equipment. Use monitoring data to verify control effectiveness, identify trends and trigger review where needed.

Written Scheme Of Control

Where risk is identified, prepare a written scheme describing:

  • Systems covered; control parameters and set points.
  • Monitoring, inspection and testing schedules and frequencies.
  • Cleaning, disinfection and maintenance procedures.
  • Start‑up/shutdown and recommissioning processes.
  • Roles, responsibilities, competence and training.
  • Action/alert levels, corrective actions and escalation criteria.

The written scheme is integral to demonstrating compliance with the Legionella Risk Assessment Legal Requirements.

Recording Significant Findings And Evidence

Where there are five or more employees, record the significant findings of the risk assessment (MHSWR regulation 3(6)). In all cases, keep sufficient detail to demonstrate a suitable and sufficient assessment and the effective operation of controls. Maintain linked documentation: risk assessment, asset registers and schematics, written scheme, monitoring and maintenance records, calibration certificates, non‑conformance logs, corrective actions, and audits. For cooling towers, retain local authority notification records.

Validation, Verification And Improvement

Validate at implementation that controls achieve intended outcomes (e.g. confirm temperature regimes; establish baseline microbiological status for cooling systems). Verify ongoing performance through routine monitoring and periodic audit. Investigate deviations promptly, implement corrective actions and confirm effectiveness with follow‑up checks. Treat the assessment and written scheme as living documents, improving them when evidence indicates better control is achievable.

Documentation & Evidence

Maintain organised, current documentation to demonstrate compliance with the Legionella Risk Assessment Legal Requirements:

  • Legionella risk assessment: scope and methodology; asset register and schematics; hazard evaluation; conclusions on reasonably foreseeable risk; prevention and control decisions with justification; residual risk; review interval and triggers; assigned responsibilities.
  • Written scheme of prevention and control: systems covered; control parameters; monitoring/inspection/testing schedules; cleaning and disinfection procedures; commissioning/decommissioning; corrective actions and escalation; roles, competence and training.
  • Appointments and competence: appointment letters for the responsible person and deputies; employee training and competence records; due diligence for consultants and water treatment providers (qualifications, training, equipment).
  • Monitoring and maintenance records: temperature profiles; flushing logs; inspections of tanks and calorifiers; biocide residuals and chemistry logs; conductivity/bleed control (cooling); corrosion/scale indicators; cleaning/descaling records; microbiological results (as applicable); calibration certificates for thermometers, test kits and meters.
  • Change control and incidents: system modifications, shutdowns and recommissioning, deviations and non‑conformances, corrective actions taken and verification of effectiveness.
  • Audits and management reviews: audit reports against ACOP L8/HSG274 and the written scheme; management review minutes; trend analyses and improvement actions.
  • Notifications and reporting: local authority notification for cooling towers and evaporative condensers (where applicable); RIDDOR reports (if required).

Retention (HSE ACOP L8/HSG274):

  • Keep the legionella risk assessment and written scheme while current.
  • Keep results of monitoring, inspections, tests and checks for at least five years.

Review Frequency & Triggers

Review the legionella risk assessment regularly and specifically when there is reason to suspect it is no longer valid or after significant change (COSHH regulation 6(3); MHSWR regulation 3(3)). Set a routine review interval proportionate to system complexity and risk (e.g. annually for complex or higher‑risk systems; longer intervals may be justified for simple, low‑risk systems with stable control), and document the rationale to meet the Legionella Risk Assessment Legal Requirements.

Typical triggers include:

  • Changes to the water system or its operation (refurbishment, extensions, replacement of plant, changes to control philosophy, decommissioning/commissioning).
  • Changes to the use of the building or occupancy patterns (extended low use, reoccupation, conversion to healthcare or residential care).
  • New information about risks or control measures (e.g. updated HSG274 guidance).
  • Monitoring or inspection results indicating that controls are ineffective (repeated temperature non‑compliance, unsatisfactory microbiological results, fouling).
  • Changes to key personnel (responsible person and deputies) or change of service provider/contractor.
  • A case of legionellosis associated with the system.
  • Extended shutdowns and recommissioning after periods of stagnation.

Record each review, decisions made and updates to the written scheme, monitoring regime, training or resourcing.

Common Non-Compliance Issues

Frequent deficiencies relative to the Legionella Risk Assessment Legal Requirements include:

  • No suitable and sufficient risk assessment completed before work liable to expose persons takes place (contrary to COSHH regulation 6 and MHSWR regulation 3).
  • Assessing components in isolation rather than the entire system, including dead legs and low‑use outlets.
  • Absence of up‑to‑date schematics or incomplete asset registers.
  • Inadequate verification of competence for consultants/contractors; insufficient training for internal personnel (contrary to MHSWR regulation 7 and ACOP L8 expectations).
  • Conclusions of “no foreseeable risk” without evidence despite favourable growth conditions (20–45 °C, stagnation, nutrients).
  • Missing or unclear written scheme; unclear roles and responsibilities.
  • Insufficient monitoring (e.g. no temperature profiling, flushing, biocide checks or action levels) or uncalibrated/unsuitable equipment.
  • Poor record‑keeping and failure to retain records for the required periods.
  • Failure to review after system changes, personnel changes, adverse results or a related case (breaching COSHH regulation 6(3) and MHSWR regulation 3(3)).
  • For cooling systems, failure to notify cooling towers/evaporative condensers to the local authority.

Corrective approach: commission a competent assessment covering all relevant systems and activities; produce schematics and a full asset register; develop a proportionate written scheme linked to assessment findings; train and resource the responsible person and teams; implement risk‑based monitoring with clear action levels; keep and retain records; and review promptly when triggers occur.

Enforcement & Penalties

HSE and, for certain premises, local authorities enforce HSWA, COSHH, MHSWR and related legislation. Enforcement follows HSE’s Enforcement Policy Statement and may include advice, improvement notices, prohibition notices and prosecution. Under HSWA section 33, courts may impose unlimited fines and, for certain offences, imprisonment. Where a case of Legionnaires’ disease is associated with a system, the adequacy of the risk assessment, written scheme and monitoring arrangements will be scrutinised against the Legionella Risk Assessment Legal Requirements. Certain cases of legionellosis in employees whose work involves exposure to contaminated water systems are reportable under RIDDOR 2013.

Practical Compliance Summary

  • Identify the dutyholder; appoint competent assistance and a responsible person with authority (MHSWR regulation 7).
  • Define the scope across all relevant water systems and activities (HSG274 Parts 1–3).
  • Survey the site; compile an asset register; prepare up‑to‑date schematics.
  • Identify hazards and exposure routes; assess normal and foreseeable abnormal conditions.
  • Decide if risk is reasonably foreseeable; document rationale and evidence to satisfy the Legionella Risk Assessment Legal Requirements.
  • Prevent exposure where practicable (eliminate dead legs, design out aerosol sources).
  • Where prevention is not practicable, implement proportionate control measures via a written scheme.
  • Establish monitoring, inspection and testing with alert/action levels and corrective actions; maintain calibrated equipment.
  • Train staff; consult employees/representatives; verify contractor competence.
  • Record significant findings; retain assessment/precaution records while current; keep monitoring/test records for at least five years.
  • Validate controls on implementation; verify effectiveness through routine monitoring and audits.
  • Review regularly and on triggers (system or use changes, adverse results, personnel changes, related disease case).
  • Notify cooling towers/evaporative condensers to the local authority where applicable; comply with RIDDOR reporting.

References & Further Reading

Official sources

Standards

Internal related pages

  • COSHH Risk Assessment: Legal Duties And Process
  • Legionella Written Scheme Of Control: Requirements And Monitoring
  • Hot And Cold Water Systems: Temperature Control And Inspection
  • Cooling Towers And Evaporative Condensers: Compliance And Control
  • Health And Safety Risk Assessment Under MHSWR: Technical Guide
  • Asbestos Management In Non‑Domestic Premises: Duty To Manage